Chiller Tonnage Estimator

API reference

Estimate the chiller tonnage a chilled-water loop needs from its flow rate and supply/return temperatures. Gets the load in tons, kW and BTU/h, adds a design margin, suggests the next standard chiller size and estimates compressor input power.

Input

Loop Temperatures

Design Allowances

Extra capacity added on top of the calculated load. Leave 0 for the bare load.

Typical water-cooled 0.5–0.7, air-cooled 1.0–1.3. Used for compressor input power.

Output

Breakdown
PropertyValue
No data yet
Was this helpful?

More ways to use this tool

REST API

curl -X POST https://api.iotools.cloud/v1/tool/chiller-tonnage-estimator \
  -H "Authorization: Bearer YOUR_API_KEY" \
  -H "Content-Type: application/json" \
  -d '{
    "flow": "240",
    "flowUnit": "gpm",
    "supplyTemp": "44",
    "returnTemp": "54",
    "tempUnit": "f",
    "margin": "10",
    "efficiency": "0.6"
  }'

Swap in your own key from your account. The tool's fields are the body — no wrapper.

Ask an AI agent

Use the IOTools `chiller-tonnage-estimator` tool (Chiller Tonnage Estimator) on this input:

YOUR_INPUT_HERE

Paste this at any agent connected to the IOTools MCP server, then add your input.

Embed widget

<iframe
  src="https://iotools.cloud/embed/chiller-tonnage-estimator/"
  width="100%" height="520" frameborder="0" scrolling="no" loading="lazy"
  title="Chiller Tonnage Estimator — iotools.cloud"
  sandbox="allow-scripts allow-forms allow-same-origin allow-downloads allow-popups allow-popups-to-escape-sandbox"
  allow="clipboard-write"
  style="width:100%;border:1px solid #e5e7eb;border-radius:12px;overflow:hidden"></iframe>
<script src="https://iotools.cloud/embed.js" async></script>

Drop this into your own page — free, no key required, just a link back.

Cost per API/MCP callFrom 5 credits
Need more credits?View pricing

Also available with

Guides

Estimate the cooling load of a chilled-water loop from its flow rate and supply/return temperatures, and turn it into refrigeration tons, kW and BTU/h. Add a design margin to get the capacity to specify, see the next standard chiller size up, and estimate compressor input power from a kW/ton efficiency.

How to use it

  1. Enter the chilled water flow and pick its unit (GPM, L/s or m³/h).
  2. Enter the supply (leaving) and return (entering) water temperatures and pick °F or °C.
  3. Optionally set a design margin and the chiller efficiency in kW/ton.

The formula

For water, tons = GPM × ΔT(°F) / 24. The tool works in SI internally: kW = flow (L/s) × 4.186 × ΔT(K), then divides by 3.517 kW per ton. One ton of refrigeration is 12,000 BTU/h.

Design margin and standard sizes

The Design Load is the calculated load plus your margin. The Suggested Chiller Size is the smallest common nominal capacity (5, 7.5, 10 … 1000 tons) that covers it. Manufacturers' real model sizes vary, so treat it as a starting point.

Limits

Assumes plain water. Glycol mixtures carry less heat per unit flow, so the real load is lower than shown for the same flow and ΔT. It does not model part-load behaviour, condenser conditions or pump heat.

Privacy

Everything runs in your browser — nothing you enter is sent anywhere.

Size the load from the building side with the HVAC BTU Load Calculator, or check the air side with the Duct Velocity Calculator.

chiller tonnagechilled waterrefrigeration tonscooling loadgpm delta thvacchiller sizingkw per tonbtu per hour